Hawkins Electrical Guide v. 02 (of 10)
305,355 chars · English
The Project Gutenberg eBook of Hawkins Electrical Guide v. 02 (of 10)
This eBook is for the use of anyone anywhere in the United States and
most other parts of the world at no cost and with almost no restrictions
whatsoever. You may copy it, give it away or re-use it under the terms
of the Project Gutenberg License included with this eBook or online
at www.gutenberg.org. If you are not located in the United States,
you will have to check the laws of the country where you are located
before using this eBook.
Title: Hawkins Electrical Guide v. 02 (of 10)
Author: N. Hawkins
Release date: May 2, 2015 [eBook #48846]
Most recently updated: October 24, 2024
Language: English
Other information and formats: www.gutenberg.org/ebooks/48846
Credits: Produced by Juliet Sutherland, Wayne Hammond and the Online
Distributed Proofreading Team at http://www.pgdp.net
*** START OF THE PROJECT GUTENBERG EBOOK HAWKINS ELECTRICAL GUIDE V. 02 (OF 10) ***
THE THOUGHT IS IN THE QUESTION THE INFORMATION IS IN THE ANSWER
HAWKINS
ELECTRICAL GUIDE
NUMBER
TWO
QUESTIONS
ANSWERS
&
ILLUSTRATIONS
A PROGRESSIVE COURSE OF STUDY
FOR ENGINEERS, ELECTRICIANS, STUDENTS
AND THOSE DESIRING TO ACQUIRE A
WORKING KNOWLEDGE OF
ELECTRICITY AND ITS APPLICATIONS
A PRACTICAL TREATISE
by
HAWKINS AND STAFF
THEO. AUDEL & CO. 72 FIFTH AVE. NEW YORK.
COPYRIGHTED, 1914,
BY
THEO. AUDEL & CO.,
NEW YORK.
Printed in the United States.
TABLE OF CONTENTS
GUIDE NO. 2.
=THE ARMATURE= 221 to 228
Definition--=how continuous current is obtained=--type
of armature--comparison ring and drum armatures--=why drum
armature is the prevailing type=--disc armatures--why disc
armatures were abandoned.
=ARMATURE WINDINGS= 229 to 256
Preliminary considerations--=winding diagrams and winding
tables=--lap and wave winding--angular pitch or spread of
drum coils--parallel or =lap winding=--series or =wave
winding=--double-windings--Siemens winding--objection
to Siemens winding--=chord winding=--multiplex
windings--number of brushes required--number of armature
circuits--=equalizer rings=--=drum winding
requirements=.
=THEORY OF THE ARMATURE= 257 to 282
Current distribution in ring and drum armatures--=connection
of brushes=--variation of voltage around the
commutator--=cross magnetization=; field
distortion--remedies for field distortion--angle of
lead--demagnetizing effect of armature reaction--=effect of
lead=--=eddy currents=; lamination--remedy for eddy
currents--magnetic drag on the armature--smooth and slotted
armatures--comparison of smooth and slotted armatures--magnetic
=hysteresis= in armature cores--=core loss= or iron
loss--dead turns--friction.
=COMMUTATION AND THE COMMUTATOR= 283 to 302
=Period of commutation=--commutating
plane--normal neutral plane--neutral plane--plane
of maximum induction--commutation--position
of the brushes--=sparking=--effect of
self-induction--construction of commutators--=points
relating= to commutators--types of commutator.
=BRUSHES AND THE BRUSH GEAR= 303 to 320
Classification--gauze brushes--wire brushes--strip
brushes--=carbon brushes=--adjustment--comparison of
copper and carbon brushes--size of brushes--number--=contact
angle of brush=---brush contact--drop in voltage at
brushes--=brush holders=--brush rigging--multipolar brush
gear.
=ARMATURE CONSTRUCTION= 321 to to 348
Parts--shaft--core--slotted core--=core
laminations=--core bolts--attachment to
shaft--insulation of core discs--teeth--advantages and
defects of slotted armatures--slotted cores; built
up construction--=ventilation=--=insulation
of core=--armature windings--construction of
inductors--objection to copper bars--=various windings=:
hand winding--evolute or butterfly winding--connectors--barrel
winding--bastard winding--former winding--former
coils--peculiarity of evolute coil--"straight out"
coil--=coil retaining devices=--driving horns.
=MOTORS= 349 to 388
Definition--=principles=--propelling drag--essential
requirements of construction--=the reverse electromotive
force=--hydraulic analogy--action of current supplied
to motor--=armature reaction= in motors--method
of starting a motor---classes of motor; =series,
shunt, and compound=--power of a motor--brake horse
power--mutual relations of motor torque and speed--=speed
regulation=--series parallel controller--=interpole
motors=.
=SELECTION AND INSTALLATION= 389 to 406
=General conditions governing
selection=--=construction=--efficiency--adaptation of
series and shunt motors--location--foundations--=erection
of dynamos and motors=--connecting up dynamos--marine
generating set--belt clamp--belt lacing--belt
speed--=points relating to belts=--gear drive--friction
drive--=electrical connections=.
=AUXILIARY APPARATUS= 407 to 430
=Switches=--switch classification and
construction--difficulty encountered in opening the
circuit--=various switches=: knife, snap, and
quick break types--=fuses=--circuit breakers:
maximum, minimum, reverse current, maximum and reverse
current, no voltage breaker--=discriminating cut
out=--time limit attachments--=rheostats=--starting
boxes--=switchboards=.
CHAPTER XVII
THE ARMATURE
The armature of a dynamo consists of coils of insulated wire wound
around an iron core, and so arranged that electric currents are induced
in the wire when the armature is rotated in a magnetic field or the
field magnets rotated and armature held stationary.
The commutator is in fact a part of the armature, but is of
sufficient importance to be considered in a separate chapter.
=Ques. What are the practical objections to the elementary armature,
described in fig. 165?=
Ans. It induces a very feeble current, which is not of constant
pressure, but pulsating; that is, it consists of two pronounced
impulses in each revolution as shown in fig. 168.
=Ques. Why does the elementary armature produce a pulsating
current?=
Ans. The pulsations are due to the coil moving alternately into, and
out of, the positions of best and least action in the magnetic field.
=Ques. How is a continuous current, or one of uniform pressure
obtained?=
Ans. If an additional coil be added to the elementary armature, at
right angles to the existing coil, and its ends suitably connected
to a four part commutator, as in fig. 185, so that one coil is in
the position of best action, while the other is in the position of
least action, the pulsations of the resulting current will be of
less magnitude. By increasing the coils and suitably altering the
construction of the commutator to accommodate the ends of these coils,
the resultant current may be represented by practically a straight
line, indicating the so called _continuous current_, instead of the
wavy resultant curve No. 6, as illustrated in fig. 187.
[Illustration: FIG 247.--Ring armature of four pole dynamo:
diagram of winding and connections, showing direction of the induced
currents. The currents in the windings under the upper N and S poles
are opposed to each other and flow to the external circuit by the
positive brush 1, and back to this half of the armature by the negative
brushes 3 and 4. At the same instant the opposed currents in the lower
windings flow to the external circuit by positive brush 2 and return
to the armature through negative brushes 3 and 4. The armature is
thus divided into four circuits and four brushes are required which
must be placed between the poles so as to short circuit the coils as
they pass through the neutral space. In this form of winding there is
no difference of potential between the + brushes, so that they are
connected in parallel, as are also the negative brushes, and then
to the external circuit. In multipolar machines there are as many
brushes as pole pieces. Since opposite commutator bars are of the
same potential on this four pole dynamo they may be joined by a cross
connecting wire and two brushes, as 2 and 4, dispensed with. This can
only be done when there is an even number of coils. The armature is
said to be "cross connected."]
An armature for practical use has a large number of coils,
suitably arranged upon an iron core, so that a large proportion
of them are always actively cutting the lines of force, or
moving into the positions of best action in the magnetic field.
=Types of Armature.=--Although there are many forms of armature,
all may be divided into three classes, according to the arrangement of
the coils or winding on the core, as:
1. Ring armatures;
2. Drum armatures;
3. Disc armatures.
Each of these forms of armature has its own special advantages
for particular purposes, the disc type being least in favor and
not having had any extensive application in this country.
[Illustration: FIG. 248.--Early form of Gramme ring armature,
the core being shown cut through, and some of the coils displaced to
make it clearer. The core, F, consists of a quantity of iron wire
wound continuously to form a ring of the shape shown by the section.
Over this is wound about thirty coils of insulated copper wire, B C D,
etc., the direction of the winding of each being the same, and their
adjacent ends connected together. The commutator segments consist of
a corresponding number of brass angle pieces, _m_, _n_, which are
fixed against the wooden boss, _o_, carried on the driving shaft.
The junction of every two adjacent coils is connected to one of the
commutator segments, as shown at _n_.]
=Ques. What is the comparison between ring and drum armatures?=
Ans. The drum armature is electrically and mechanically the more
efficient, possessing, as it does, possibilities in the way of better
mechanical construction of the core, and in the arrangement and fixing
of the inductors thereon not to be found in the ring form. Less wire
and magnetizing current are required for the field magnets for a given
output than with the ring armature. Drum winding is not so simple as
ring winding, and it is more difficult to ventilate a drum than a ring
armature, it being necessary to provide special ventilating ducts.
[Illustration: FIG. 249.--Modern form of Gramme ring armature.
The core consists of a number of thin flat rings of well annealed
charcoal iron, the outer diameter of each ring or disc being 11½
inches, and its inner diameter 9¼ inches. Sheets of thin paper
insulate each disc from its neighbors to prevent the flow of eddy
currents. The armature is mounted on a steel shaft to which is keyed
a four armed metal "spider," the extremities of whose arms fit into
notches cut in the inner edges of the soft iron core rings, so that a
good mechanical connection is obtained between the core and the shaft.
The spider is made of a non-magnetic metal, to reduce the tendency to
leakage of lines of force across the interior of the armature. The
armature inductors consist of cotton covered copper wire of No. 9
standard wire gauge, wound around the core in one layer, and offering
a resistance, from brush to brush, of 0.048 ohm. There are two
convolutions in each section, the adjacent ends of neighboring sections
being soldered to radial lugs projecting from the commutator bars.]
=Ques. Describe a ring armature.=
Ans. It consists essentially of an iron ring, around which is wound
a number of coils. These various coils are wound on separately, the
wire being carried over the outside of the ring, then through the
center opening and again around the outside, this operation being
repeated until the winding for that individual section is completed.
The adjacent coil is then wound in the same way, the ends of each being
brought out to the commutator side of the armature, the arrangement of
the coils on the ring and connections with the commutator being shown
in fig. 247, examples of actual construction being shown in figs. 248
and 249.
=Ques. For what conditions of operation is the ring armature
specially adapted, and why?=
Ans. It is well suited to the generation of small currents at high
voltage, as for series arc lighting, because the numerous coils can be
very well insulated.
[Illustration: FIG. 250.--Distribution of magnetic lines of
force through a Gramme ring. Since the metal of the ring furnishes a
path of least reluctance, most of the magnetic lines will follow the
metal of the ring and very few will penetrate into the aperture of
the interior. This condition causes a serious defect in the action of
ring armatures rendering the winding around the interior useless for
the production of electromotive force. Hence, in ring armatures only
about half of the winding is effective, the rest or "dead wire," adding
its resistance to the circuit, thus decreasing the efficiency of the
machine.]
=Ques. Why does a ring armature require more copper in the winding
than a drum armature?=
Ans. For the reason that those inductors which lie on the inner side of
the iron ring, being screened from practically all the lines of force,
as shown in fig. 250, do not generate any current.
Numerous attempts have been made to utilize this part of the
winding by making the pole pieces extend around the ring in
such a manner that lines of force will pass to the inside of
the ring, also by arranging an additional pole piece on the
inside of the armature, but mechanical considerations have
shown these methods to be impractical.
=Ques. Is any portion of the winding of a drum armature inactive?=
Ans. Yes; the end connectors do not generate any current.
[Illustration: FIG. 251.--Illustrating the principle of
Siemens' drum winding. In order to make the winding and connections
clear, one coil and the commutator is shown assembled, although the
latter is not put in place until after all the sections have been
wound, the ends of the wires being temporarily twisted together until
all can be soldered to the risers. The cores of these early machines
were of wood overspun circumferentially with iron wire before receiving
the longitudinal copper windings.]
=Ques. What is the chief advantage of the drum armature?=
Ans. It reduces considerably the large amount of dead wire necessary
with the ring type.
=Ques. How is this accomplished?=
Ans. By winding the wire entirely on the outer surface of a cylinder or
_drum_, as it is called, as shown in fig. 251, thus none of the wire is
screened by the metal of the core.
[Illustration: FIG. 252.--Elementary four coil drum winding,
showing the connections with the commutator segments, and directions of
currents in the several coils. The action of this type of armature is
fully explained in the text.]
Fig. 252 shows an elementary four coil drum armature. Starting
from the point _a_ and following the winding around without
reference at first to the commutator, it will be found that the
rectangular turns of the wire form a closed circuit, and are
electrically in series with one another in the order of the
numbers marked on them.
With respect to the connections to the four segments _w_, _x_,
_y_, _z_, of the commutator it will be found that at two of
these, _x_ and _y_, the pressures in the windings are both
directed _from_, or both directed _toward_ the junction with
the connecting wire. At the other two segments, _z_ and _w_,
one pressure is toward the junction and the other directed from
it. If, therefore, the brushes be placed on _x_ and _y_ they
will supply current to an external circuit, _z_ and _w_, for
the moment being idle segments.
=Disc Armatures.=--The inductors of a disc armature move in a
plane, perpendicular to the direction of the lines of force, about an
axis parallel to them as shown in fig. 253. The main difficulty with
this type has been in constructing it so that it will be strong and
capable of resisting wear and tear. It was introduced in an effort to
avoid the losses due to eddy currents and hysteresis present in the
other types of armature.
[Illustration: FIG. 253.--Disc armature of Niaudet. It is
equivalent to a ring armature, having the coils turned through an angle
of 90°, so that all the coils lie in a plane perpendicular to the axis
of rotation. The connections of the coils with each other and with
the commutator remain the same, the beginning and the end of adjacent
coils leading to a common commutator bar as shown. The magnetic field
is arranged by the use of two magnets, so arranged as to present the
north pole of one to the south pole of the other, and _vice versa._ In
the figure one of these magnets is considered as above the paper, and
the other below. If this armature be rotated through the magnetic field
as shown, a reversal of current takes place in each coil, when it is in
such a position that one of its diameters coincides with the pole line,
_NS_. If the brushes be set so as to short circuit the coils that are
in this position, the armature will be divided into two branchings, the
current flowing in an opposite direction in each, and a direct current
will flow in the exterior circuit.]
On account of the nature of the construction of a disc
armature, it is necessary that the coils subject to induction
occupy as small a space as possible in the direction of their
axes. This requirement, as well as the connection of the
inductors with each other and with the commutator, prevented
the general adoption of this form of armature, and subsequent
experience failed to justify the existence of the type.
CHAPTER XVIII
ARMATURE WINDINGS
To connect up rightly the inductors on an armature so as to produce
a desired result is a simple matter in the case of ring winding, for
bipolar or multipolar machines. It is a less easy matter in the case
of drum winding, especially for multipolar machines. Often there are
several different ways of arriving at the same result, and the fact
that methods which are electrically equivalent may be geometrically and
mechanically different makes it desirable to have a systematic method
of treating the subject.
The elementary arrangement of drum and disc armatures has already been
considered, which is sufficient explanation for small armature coils
of only a few turns of wire, but in the case of larger machines which
require many coils, further treatment of the subject is necessary.
For example, in order to direct the winder how to make the
connections for, say a four pole machine having 100 bars spaced
around its armature, some plain method of representing all the
connections so that they may be easily understood is necessary.
From this the workman finds out whether he is to connect the
_front_[A] end of bar No. 1 across to 50 or across a quarter
of the circumference to 24, or across three quarters of it to
bar 75. Again, he ascertains to which bar he is to connect the
_back_[1] end of the bar, and how the bars are to be connected
to the commutator.
[1] NOTE:--The "front" end means the end at which the commutator is
located. Armatures are most conveniently regarded from this end, the
opposite end being known as the "back" end.
=Winding Diagrams and Winding Tables.=--In the construction of
armatures, instructions to winders are given in the form of diagrams
and tables. In the tables the letters F and B stand for _front_ and
_back_, meaning _toward_ the front end, and _from_ the front end
respectively. The letters U and D stand for _up_ and _down_.
[Illustration: FIG. 254.--End of ring winding for a four
pole machine. An end view is simply a view showing the arrangement
of the armature inductors and connections _looking from the front or
commutator end_. A developed view of the above winding is shown in fig.
257.]
There are three kinds of winding diagram:
1. End view diagram;
2. Radial diagram;
3. Developed diagram.
The end view is simply a view showing the arrangement of the armature
inductors and connections looking from the front or commutator end,
such as shown in fig. 254.
In the radial diagram the inductors of the armature are represented by
short radial lines, while the end connectors are represented by curves
or zigzags, those at one end of the armature being drawn within, those
at the other end, without the circumference of the armature. With the
radial diagram it is easier to follow the circuits and to distinguish
the back and front pitch of the winding.
[Illustration: FIG. 255.--Partial sketch of a four pole
machine laid on its side. If the observer imagine himself placed at the
center, and the panorama of the four poles to be then laid out flat,
the developed view thus obtained would appear as in fig. 256.]
The developed diagram is a mode of representation, originally suggested
by Fritsche of Berlin, in which the armature winding is considered as
though the entire structure had been developed out of a flat surface.
This is best explained by aid of figs. 255 and 256.
If in fig. 255, which represents an armature core and a four
pole field, wires _a_ and _c_ be placed parallel to the axis of
the armature to represent two of the armature inductors, and
moved along the air gap space clockwise past the S poles,
they will cut magnetic lines inducing electromotive forces in
the directions indicated. To attempt to show a large number of
inductors in a drawing of this kind would be unintelligible.
Accordingly, the observer is considered as being placed at the
center of the armature, and the panorama of the four poles
surrounding him to be then laid out flat or "developed" as in
fig. 256.
The faces of the N and S poles are shaded obliquely for
distinction. By choosing the proper directions for these
oblique lines, a piece of paper having a narrow slit to
represent the wire may be laid over the drawing of the pole and
when moved, as indicated by the dotted arrows to the right, the
slit in passing over the oblique lines will cause an apparent
motion in the direction in which the current in reality tends
to flow. It is easily remembered which way the oblique lines
must slope, for those on the N pole slope parallel to the
oblique part of the letter N.
=Lap Winding and Wave Winding=.--In winding armatures there are
two distinct methods employed, known respectively as _lap_ and _wave
winding_. The distinction arises in the following manner: Since the
inductors, in passing a north pole generate electromotive forces in one
direction, and in passing a south pole generate electromotive forces in
the opposite direction, it is evident that an inductor in one of these
groups ought to be connected to one in nearly a corresponding position
in the other group, so that the current may flow down one and up the
other in agreement with the directions of the electromotive forces. The
order followed in making these connections gives rise to lap and wave
windings.
[Illustration: FIG. 256.--Developed view of the four pole
field shown in perspective in fig. 255.]
=Ques. What is lap winding?=
Ans. _One in which the ends of the coils come back to adjacent segments
of the commutator; the coils of such a winding lap over each other._
=Ques. What is a wave winding?=
Ans. _One in which the coil ends diverge and go to segments widely
separated, the winding to a certain extent resembling a wave._
[Illustration: FIG. 257.--Development of ring winding of four
pole machine shown in fig. 254. The dead wire or inactive inductors
on the inside of the ring are shown in dotted lines, the full lines
representing the active portion of the winding.]
=Angular Pitch or Spread of Drum Coils.=--Before taking up
the winding as a whole, the form of the individual coil should be
considered. Fig. 260 shows an end view of one coil in position on a
drum armature of a multipolar machine. The two slots X and Y contain
the sides of the coil and the distance between them on the surface
of the drum is called the _angular pitch_ or _spread of the coil_.
Theoretically this is equal to the pitch of the poles, represented by
the angle M, which is the angle between the pole centres.
[Illustration: FIGS. 258 and 259.--Wooden armature core and
winding table for practice in armature winding. By using strings of
different colors to represent the various coils, the path of each coil
is easily traced when the winding is completed, as in fig. 263.]
For instance, on a four pole machine the pitch would be 90°,
on a six pole machine, 60°, etc. Usually the angular pitch of
the coil is made just a little less than the pole pitch of the
machine, in order to shorten the end connections of the coils
from slot to slot. However, if the angular pitch be made too
small trouble will be encountered in commutation.
In addition to the angular pitch there is the _commutator
pitch_ which relates to the distance around the commutator
bridged by the ends of the coil. Thus, if the commutator
segments were numbered consecutively 1, 2, 3, etc., and the
_commutator pitch_ say is 10, it would signify that one end
of the coil was connected to segment 1 and the other end to
segment 11; the ends of the next coil in order then would be
connected to segments 2 and 12, in each case there would be ten
segments between the two segments connecting with the coil ends.
[Illustration: FIG. 260.--End view of drum armature of a
multipolar machine showing one coil in position to illustrate the
_angular pitch_ or spread of drum coils.]
=Parallel or Lap Drum Winding.=--In order to avoid much of the
difficulty usually experienced by students of drum winding, the
beginner should construct for himself a wooden armature core upon
which he can wind strings of various colors, or wires with distinctive
insulation, to represent the numerous coils that are used on real
armatures. A few windings attempted in this way will make clear many
points that cannot be so easily grasped from a written description.
The type of drum core best adapted for this work is the slotted variety
as shown in fig. 258, as it will facilitate the winding. The core as
shown in the illustration has twelve slots and six commutator segments,
the number of each required for the example of lap winding indicated in
the winding table fig. 259.
In making the wooden core, the slots may be formed by nailing a
series of thin strips around a cylindrical piece of wood, thus
avoiding the trouble of cutting grooves. In the illustrations
the commutator segments are shortened (leaving no room for
brushes) in order to show the connections as clearly as
possible.
[Illustration: FIG. 261.--Developed view of a typical lap
winding. From the figure it is seen that at the back of the armature
each inductor is united to one five places further on, that is, 1 to 6,
3 to 8, etc., and at the front end of the winding, after having made
one "element," as for example _d_-7-12-_e_, then forms a second element
_e_-9-14-_f_ which "laps" over the first, and so on all around until
the winding returns on itself.]
=Ques. Describe the simple lap winding fig. 259.=
Ans. As given in the table, it consists of six loops of wire presenting
twelve inductors on the cylindrical surface of the core or drum. In the
table, six wires are shown, having distinctive and varied insulation
so as to readily distinguish the different coils. Opposite these are
letters and figures designating the path and connections of each coil.
=Ques. What is the path of the first coil?=
Ans. According to the table it is:
A — 1 — 6 — B
that is, one end of the wire is connected to commutator segment A (fig.
262) and then wound to the back of the drum through slot 1, across
the back of the drum to slot 6, returning through this slot, and then
connected with commutator segment B.
[Illustration: FIG. 262.--Skeleton view of wooden armature
core showing in position the first two coils of the winding indicated
in the table fig. 259.]
=Ques. Describe the path of the second coil.=
Ans. The second coil, having the block insulation, is wound according
to the table, in the order:
B--3--8--C
that is, beginning at segment B, thence to back of drum through slot 3,
across the back to slot 8, returning through this slot and ending at
segment C.
The completed winding of the first two coils are shown in fig.
262, the drum being shown in dotted lines so that all of each
coil may be visible.
[Illustration: FIG. 263.--View of completed winding as
indicated in the table fig. 259. Thus the path of the first coil,
according to the table is A-1-6-B which means that the coil begins at
segment A of the commutator, rises to slot 1, and proceeds through the
slot to the back of the drum; thence across the back to slot 6, through
the slot and ending at segment B. The other coils are wound in similar
order as indicated in the table.]
=Ques. How are the remaining coils wound on the drum?=
Ans. Each of the succeeding coils are wound as indicated in the table,
the last connection being made to segment A, the one from which the
winding started.
=Ques. What is the general form of the completed winding?=
Ans. It may be considered simply as a wire wound spirally around the
drum, with loops brought down to the commutator segments, and ending at
the segment from which the start was made.
The completed winding as indicated by the table is shown in
fig. 263. Here the path of each coil is easily distinguished by
means of the varied insulations although in part hidden by the
drum. Fig. 264 shows a developed view of the winding.
[Illustration: FIG. 264.--Developed view of the winding shown
in perspective in fig. 263.]
=Ques. What condition must obtain in winding an even number of
coils?=
Ans. The wire must not be wound around the drum to diametrically
opposite positions, as for instance 1 to 7 in fig. 265.
=Ques. Why is this?=
Ans. The reason will be clearly seen by attempting the winding on the
wooden core. A winding of this kind on the drum fig. 258, would proceed
as follows:
A--1-- 7--B
B--3-- 9--C
C--5--11--D
In order now to continue winding in a regular way, the wire from
segment _d_ should pass to the rear of the armature along space 7,
but this space is already occupied by the return of the first coil.
Continuing the winding from this point, it would be necessary to carry
the wire from segment _d_ to 6 or 8, _resulting in an unbalanced
winding_.
[Illustration: FIG. 265.--Lap winding for bipolar machine,
with uneven number of coils; in this case the rear connectors may be
made directly across a diameter as shown.]
=Ques. How is a symmetrical winding obtained having an even number of
coils?=
Ans. The inductors, in passing from the front to the rear of the
armature, fig. 263, must occupy positions 1, 3, 5, 7, 9, 11, and the
even numbered positions will then serve as the returns for these wires.
In the example here shown there are six coils, comprising
twelve inductors and six commutator segments; it should be
noted, however, that if there were an uneven number of coils,
the rear connections could be made directly across a diameter
as shown in fig. 265, which would give a symmetrical winding.
With ten slots as shown in the figure, the drum would be wound,
for a bipolar machine, according to the following table:
A--1-- 6--B
B--3-- 8--C
C--5--10--D
D--7-- 2--E
E--9-- 4--F
[Illustration: FIG. 266.--Developed view of a typical wave
winding. This winding, instead of lapping back toward the commutator
segment from whence it came, as in lap winding, turns the other way.
For instance, _d_-7-12 does not return directly to _e_, but goes on to
_i_, whence another element _i_-17-4-_e_ continues in a sort of zigzag
_wave_.]
=Ques. Are coils such as shown in figs. 263 and 265 used in
practice?=
Ans. No, for practical use each coil would consist of several turns,
the diagram then merely indicates the end connections and slots for the
several turns of each coil.
=Series or Wave Drum Winding.=--In this mode of winding, the
inductors are arranged around the armature so that they do not turn
back, thus describing a zigzag or _wave-like_ path; that is, the coil
ends instead of connecting with adjacent segments of the commutator,
are attached to segments more or less remote.
=Ques. Describe the circuits of a simple or simplex wave winding.=
Ans. Only two sets of brushes are required for such a winding, but as
many brushes as there are poles can be used.
[Illustration: FIG. 267.--Five coil wave winding for a four
pole machine. In this winding only two brushes are used, there being
only two paths through the armature.]
=Ques. For what service are wave windings adapted?=
Ans. They are generally used on armatures designed to furnish a current
of high voltage and low amperage.
An example of wave drum winding for a four pole machine is
shown in fig. 267. For simplicity, very few coils are taken,
there being only five as shown in the illustration. To make the
winding, one strip should be removed from the wooden core and
the others spaced equally around the cylindrical surface. This
will give ten slots, the number required for the five coils.
The winding is indicated in the following table:
A--1-- 4--C
B--3-- 6--D
C--5-- 8--E
D--7--10--A
E--9-- 2--B
Accordingly the first coil starting at segment A, is carried
to the back of the drum through slot 1, thence across the back
and returning through slot 4, ending at segment C the starting
point of the second coil. Each coil is wound on in similar
manner, the last coil ending at segment A, the starting point
of the first coil. A developed view of the winding is shown in
fig. 268.
=Double Windings.=--In the various drum windings thus far
considered, each coil had its individual slots, that is, no two
occupied the same two slots. This arrangement gave twice the number of
slots as commutator segments.
[Illustration: FIG. 268.--Developed view of the five coil wave
winding shown in fig. 267.]
In a double winding there are as many segments as slots, each of the
latter containing two inductors, comprising part of two coils.
=The Siemens Winding.=--In winding drum armatures for bipolar
dynamos of two horse power or less, and especially for very small
machines as used in fan or sewing machine motors, a form of winding,
known as the Siemens winding, which is shown in fig. 271, is largely
used. It consists in dividing the surface of the armature core in one
equal number of slots, say 16, and using a 16 part commutator.
In the Siemens winding, the end of the wire used at the start
is to be connected to the first commutator bar, but must be
fastened to the armature core out of the way so as not to
interfere with the winding of the coils.
If eight turns of wire be required to fill a slot with one
layer, then the wire is carried from front to back and bent
aside so as to clear the shaft; after passing across the back
or pulley end of the armature, it is wound in the diametrically
opposite section and brought to the front, then across the
commutator end and up close to the beginning of the coil.
[Illustration: FIG. 269.--Series connected wave wound ring
armature for a four pole machine. The coils are so connected that only
two brushes are necessary.]
Since eight turns are to be used, the process of winding
is continued until the section is full and the end of the
coil will lie in a position ready to begin the next section.
Sometimes the wire is cut at this part of the coil leaving 3 or
4 inches projecting for connecting to the commutator bar 2, or
next to the first bar where the winding was started.
The usual practice is, however, to make a loop of the wire of
sufficient length to make the connection to the commutator
and it has the advantage that since all of the coils on the
armature are joined in series, the ending of one coil is joined
to the beginning of the next which avoids making mistakes in
making the commutator connections.
If the ends be cut they should be marked "beginning" and
"end" to avoid trouble, because if they get mixed, it will be
necessary to test each coil with a battery and compass needle
in order to determine the polarity produced and find which is
the beginning of the coil and which the end. With 32 ends
of the wire projecting from the end of the armature, it is
confusing and mistakes are often made in the connections, so
that one or more coils may oppose each other which would reduce
the voltage.
After the surface of the armature is covered with one layer it
will be noticed that the number of leads from the coils to the
commutator bars is only one-half the number of bars and that
they lie on one-half of the armature.
In order to complete the winding the first layer should be
insulated and the second layer wound on. The beginning of the
new coil will be directly over the first coil put on, but the
beginning of the new coil will be diametrically opposite the
beginning of the first coil wound.
The winding is now continued section by section and as each
coil is finished a loop or pair of leads is left to connect to
each bar. When the last coil is wound, its end will be found
lying next to the wire used in starting and should be joined to
it and finally connected to bar number one where the start was
made.
[Illustration: FIG. 270.--Developed view of the series
connected wave wound ring armature shown in fig. 269.]
With the winding and commutator connected, all of the coils are
in series and the beginning of the first coil joins the end of
the last coil.
If a pair of brushes be now placed on the commutator at
opposite points the current will flow into the bar and then
divide between the two leads connected to it, half of the
current flowing around one side and the other half flowing
around the other half of the armature or in other words, the
two halves of the armature are joined in parallel.
=Ques. What is the objection to the Siemens winding just
described?=
Ans. It produces an unsightly head where the wires pass around the
shaft and requires considerable skill to make it appear workmanlike.
=Ques. How may this be avoided?=
Ans. By using the chord windings of Froehlich or Breguet, which are
improvements over the Siemens in appearance and are more easily carried
out.
[Illustration: FIG. 271.--End view of an armature, showing the
distinction between Siemens' winding and chord winding.]
=Chord Winding.=--In cases where the front and back pitches[2] are
so taken that the average pitch differs considerably from the value
obtained by dividing the number of inductors by the number of poles,
the arrangement is called a chord winding.
[2] NOTE--The term _back pitch_ means the number of _spaces_ between
the two inductors of a coil. For instance, in fig. 267, the pitch
is 3; that is, there are three spaces between say inductors 1 and 4
which form part of the coil A--1--4--C. It is called the back pitch
in distinction from the _front_ or commutator pitch, which in this
instance is 2.
In this method each coil is laid on the drum so as to cover an arc of
the armature surface nearly equal to the angular pitch of the poles; it
is sometimes called _short pitch winding_.
=Ques. What is the difference between the Siemens winding and the
chord winding?=
Ans. This is illustrated in fig. 271, which shows one end of an
armature. In the Siemens winding, a wire starting, say at A, crosses
the head and enters the slot marked B. If it enters slot C it is a
chord winding.
=Ques. Describe a chord winding.=
Ans. The winding is started in the same manner as described in the
Siemens method, only instead of crossing the head and returning in
the section diametrically opposite, the section _A C_, fig. 271, next
to it is used for the return of the wire to the front end. Leads for
connecting to the commutator are left at the beginning and end of
each section as before stated and the only difference between the two
methods will be noticed when the first layer is nearly complete in that
two sections lying next to each other have no wire in them. This will
cause the winder to think he has made a mistake, but by continuing the
winding and filling in these blank spaces in regular order when the two
layers are completed, all the sections will be filled with an equal
number of turns and there will be the required number of leads from the
coils to connect up to the commutator bars.
=Ques. How many paths in the chord winding just described?=
Ans. Two.
=Multiplex Windings.=--An armature may be wound with two or more
independent sets of coils. Instead of independent commutators for the
several windings, they are combined into one having two or more sets
of segments interplaced around the circumference. Thus, in the case of
two windings, the brush comes in contact alternately with segments of
each set. The brush then must be large enough to overlap at least two
segments, so as to collect current from both windings simultaneously.
Both windings then are always in the circuit in parallel.
=Ques. What is the effect of a multiplex winding?=
Ans. It reduces the tendency to sparking, because only half of the
current is commutated at a time, and also because adjacent commutator
bars belong to different windings.
[Illustration: FIG. 272.--A progressive wave winding. _If
the front and back pitches of a wave winding be such that in tracing
the course of the winding through as many coils as there are pairs of
poles, a segment is reached in advance of the one from which the start
was made, the winding is said to be progressive._ The figure shows
three coils of a winding having 18 inductors. From the definition, the
number of coils to consider to determine if the winding be progressive
is equal to the number of poles divided by 2, which in this case is
equal to 2. These coils are shown in the figure as follows: A--1--4--F
and F--11--14--B. The second coil ends at segment B which is in
_advance_ of segment A from which the winding began, indicating that
the winding is progressive. Fig. 272 is given simply to illustrate the
definition of a progressive winding, and not to represent a practical
winding.]
=Ques. Does an accident to one winding disable the machine?=
Ans. No, it simply reduces its current capacity.
=Ques. Can multiplex windings have more than two windings?=
Ans. Yes, there may be three or four windings.
=Ques. What is the objection to increasing the number of windings?=
Ans. It involves an increased number of inductors and commutator
segments, which is undesirable in small machines, but for large ones
might be allowable.
[Illustration: FIG. 273.--A retrogressive wave winding. _If
the pitches be such that in tracing the winding through as many coils
as there are pairs of poles, the first segment of the commutator is not
encountered or passed over, the winding is said to be retrogressive._
The number of coils to consider is two, as follows: A-1-4-D and
D-7-10-G. The second coil ends at G, hence, since the segment A where
the start was made has not been reached or passed over the winding is
retrogressive. Fig. 273 is given simply to illustrate the definition of
retrogressive winding, and not to represent a practical winding.]
When there are two independent windings the arrangement is
called _duplex_, with three windings, _triplex_, and with four,
_quadruplex_.
=Ques. What loss is reduced with multiplex windings?=
Ans. In these windings, the division of what otherwise would be very
stout inductors into several smaller ones, has the effect of reducing
eddy current loss.
=Ques. For what service are machines with multiplex windings
specially adapted?=
Ans. Multiplex windings are used in machines intended to supply large
currents at low voltages, such as is required in electrolytic work.
=Number of Brushes Required.=--The number of places on the
commutator at which it is necessary or advisable to place a set of
collecting brushes can be ascertained from the winding diagrams. All
that is necessary is to draw arrows marking the directions of the
induced electromotive forces. Wherever two arrow heads meet at any
segment of the commutator, a positive brush is to be placed, and at
every point from which two arrows start in opposed directions along the
winding, a negative brush should be placed.
=Ques. How many brushes are required for lap windings and ordinary
parallel ring windings?=
Ans. There will be as many brushes as poles, and they will be situated
symmetrically around the commutator in regular order and at angular
distances apart equal to the pole pitch.
It should be noted that the number of brush sets does not
necessarily show the number of circuits through the armature.
=Ques. How many brushes are required for wave windings?=
Ans. If arrows be drawn marking the direction of the induced
electromotive forces to determine the number of brushes, it will be
found that only two brushes are required for any number of poles.
=Ques. What is the angle between these two brushes?=
Ans. It is the same as the angle between any north and south pole.
For instance, in a ten pole machine with wave winding the pitch
between the brushes may be any of the following angles:
360 ÷ 10 = 36°
3 × 36° = 108°
5 × 36° = 180°
[Illustration: FIGS. 274 and 275.--Right and left hand
windings. These consist respectively of turns which pass around the
core in a right or left handed fashion. Thus in fig. 274, in passing
around the circle clockwise from _a_ to _b_, the path of the winding
is a right handed spiral. In fig. 275, which shows one coil of a drum
armature, if _a_ be taken as the starting point, in going to _b_,
_a_ must be connected by a spiral connector across the front end of
the drum to one of the descending inductors such as M, from which at
the back end another connector must join it to one of the ascending
inductors, such as S, where it is led to _b_, thus making one right
handed turn.]
Sometimes with lap winding it is desirable to reduce the number of
brushes. In fig. 276, is shown the distribution of currents in a four
pole lap wound machine having four brushes and generating 120 amperes.
In each of the four circuits the flow is 30 amperes, and the current
delivered to each brush is 60 amperes. If now two of the brushes be
removed, the current through each of the remaining two will be 120
amperes, while internally there will be only two circuits as shown
in fig. 277. It should be noted, however, that these two circuits do
not take equal shares of the current since, though the sum of the
electromotive forces in each circuit is the same, the resistance of
one is three times that of the other, giving 90 amperes in one and
30 amperes in the other, as indicated in the figure. If no spark
difficulties occur in collecting all the current with only two brushes,
the arrangement will work satisfactorily, but the heat losses will be
greater than with four brushes.
[Illustration: FIG. 276.--Distribution of armature currents
in a four pole lap wound dynamo having four brushes and generating 120
amperes.]
=Ques. Are more than two brushes ever used with wave winding?=
Ans. It is sometimes advisable to use more than two brushes with wave
windings, especially when the current is very large.
For instance, in the case of a singly re-entrant[3] simplex
wave winding for an eight pole machine, whenever any brush
bridges adjacent bars of the commutator, it short circuits one
round of the wave winding and this round is connected at three
intermediate points to other bars of the commutator. Hence, if
the short circuiting brush be a positive brush, no harm will
be done by three other positive brushes touching at the other
points. If these other brushes be broad enough to bridge across
two commutator bars, they may effect commutation, that is,
three rounds instead of one undergoing commutation together.
[3] NOTE.--A re-entrant winding is one in which both ends re-enter or
lead back to the starting point; a closed winding.
=Number of Armature Circuits.=--It is possible to have windings
that give any desired even number of circuits in machines having any
number of poles.
[Illustration: FIG. 277.--Showing effect of removing two of
the brushes in fig. 275. If no spark difficulties occur in collecting
the current with only two brushes, the arrangement will work
satisfactorily, but the heat losses will be greater than with four
brushes.]
=Ques. How many paths are possible in parallel?=
Ans. For a simplex spirally wound ring, _the number of paths in
parallel is equal to the number of poles_, and for a simplex series
wound ring, _there will be two paths_. In the case of multiplex
windings _the number of paths is equal to that of the simplex winding
multiplied by the number of independent windings_.
In large multipolar dynamos it is, as a rule, inadvisable to
have more than 100 or 150 amperes in any one circuit, except in
the case of special machines for electro-chemical work. Such
considerations are factors which govern the choice of number of
circuits.
=Equalizer Rings.=--These are rings resembling a series of
hoops provided in a parallel wound armature to eliminate the effects
of "unbalancing," by which the current divides unequally among the
several paths through the armature. By means of leads, equalizer rings
connect points of equal potential in the winding and so preserve an
equalization of current.
[Illustration: FIG. 278.--Rear view of armature of a large
dynamo built by the General Electric Co., showing equalizer rings.]
=Ques. In multipolar machines what points are connected by equalizer
rings?=
Ans. Any two or more points in the winding, that during the rotation,
are at nearly equal potentials.
If there were perfect symmetry in the field system, no currents
would flow along such connectors; however, owing to imperfect
symmetry, the induction in the various sections of the winding
may be unequal and the currents not equally distributed.
=Drum Winding Requirements.=--There are several conditions that
must be satisfied by a closed coil drum winding:
1. There cannot be an odd number of inductors;
An odd number of inductors would be equivalent to not having
a whole number of coils. The even numbered inductors may be
regarded as the returns for the odd numbered inductors.
2. Both the front and back pitches must be odd in simplex windings.
3. The average pitch should be approximately equal to the number of
inductors divided by the number of poles.
This condition =must= obtain in order that the electric
pressures induced in inductors moving simultaneously under
poles of opposite sign, will be added. The smallest pitch
meeting this condition would stretch completely across a pole
face, while the largest would stretch from the given pole tip
to the next pole tip of like polarity.
The choice of front and back pitch for a given number of inductors
should, with lap and wave windings in general, comply with the
following conditions:
1. All the coils composing the winding must be similar, both
mechanically and electrically, and must be arranged symmetrically upon
the armature.
2. Each inductor of a simplex winding must be encountered once only,
and the winding must be re-entrant.
3. Each simplex winding composing a multiplex winding must fulfill the
requirement for a simplex winding.
4. A singly re-entrant multiplex winding must as a whole satisfy the
requirement for a simplex winding.
In addition to the above requirements for lap and wave windings in
general, lap windings must comply with the following conditions:
1. The front and back pitches must be opposite in sign;
2. The front and back pitches must be unequal;
If they be equal, the coil would be short circuited upon itself.
3. The front and back pitches must differ by two;
4. In multiplex windings, the front and back pitches must differ by two
multiplied by the number of independent simplex windings composing the
multiplex winding;
5. The number of slots on a slotted armature may be even or odd;
6. The number of inductors must be an even number; it may be a multiple
of the number of slots;
In the case of wave windings the several conditions to be fulfilled may
be stated as follows:
1. The front and back pitches must be alike in sign;
2. The front and back pitches may be equal or they may differ by any
multiple of two.
They are usually made nearly equal to the number of inductors
divided by the number of poles.
CHAPTER XIX
THEORY OF THE ARMATURE
=Current Distribution in Ring and Drum Armatures.=--In studying
the actions and reactions which take place in the armature, the student
should be able to determine the directions of the induced currents. The
basic principles of electromagnetic induction were given in chapter
X, from which, for instance, the distribution of current in the
gramme ring armature, shown in fig. 279, is easily determined by the
application of Fleming's rule.
Tracing the current from the negative to the positive brush, it
will be seen that it divides, half going through coils 1, 2, 3,
and half through coils I, II, III, these two currents ascend to
the top of the ring, uniting at the positive brush.
=Ques. In the Gramme ring armature (fig. 279) what is the
distribution of armature currents?=
Ans. There are two paths in parallel as indicated in fig. 279.
=Ques. How does the voltage vary in the coils?=
Ans. It varies according to the position of the coils, being least when
vertical and greatest when horizontal in a two pole machine arranged as
in fig. 279.
The upper and lower coils in the right hand half of the ring
armature, fig. 279, will have about the same electromotive
force induced in them, say 2 volts each, while the two coils
between them will have a higher electromotive force, at the
same instant, say 4 volts each, since they occupy nearly the
positions of the maximum rate of change of the magnetic lines
threading through them. These eight coils may be represented by
two batteries connected in parallel, each battery consisting of
two 2 volt cells and two 4 volt cells as shown in fig. 280. The
voltage of each battery then will be
2 + 4 + 4 + 2 = 12 volts
[Illustration: FIG. 279.--Current distribution in a gramme
ring armature. There are two paths for the current between the brushes,
half going up each side of the ring as indicated by the arrows, thus
giving two paths in parallel as indicated in fig. 281.]
[Illustration: FIG. 280.--Battery analogy illustrating current
distribution in a ring armature. The eight coils of the armature, fig.
279, are represented by two batteries of four cells each. The action
of the two units thus connected is indicated by the arrows. In the
external circuit the voltage is equal to that of one battery and the
current is equal to the sum of the currents in each battery.]
The two batteries being connected in parallel, the voltage at
the terminals will be the same, but the current will be the sum
of the currents in each battery.
=Ques. How may the number of paths in parallel be increased?=
Ans. By increasing the number of poles.
For instance, in a four pole machine, as in fig. 283, there are
four paths in parallel. In this case the armature may be used
to furnish two separate currents, though this is not desirable.
[Illustration: FIG. 281.--Diagram showing distribution of
current in the gramme ring armature of fig. 279. The current flows in
two parallel paths as indicated.]
[Illustration: FIG. 282.--Diagram showing current distribution
through armature of a four pole machine with like brushes connected.
There are four paths in parallel, hence the induced voltage will equal
that of one set of coils, and the current will be four times that
flowing in one set of coils.]
=Ques. How are the brushes connected?=
Ans. Usually all the positive brushes are connected together, and all
the negative brushes as in fig. 283, giving four paths in parallel
through the armature as indicated in fig. 282.
[Illustration: FIG. 283.--Brush connections for four pole
dynamo. It is usual to connect all the positive brushes to one terminal
and all the negative brushes to the other which gives four parallel
paths as shown in the diagram, fig. 282. In a four pole machine, two
separate currents can be obtained by omitting the parallel brush
connections.]
=Ques. How does this method of brush connection affect the
voltage?=
Ans. The voltage at the terminals is equal to that of any of the sets
of coils between one positive brush and the adjacent negative brush.
Thus in the four pole machine, fig. 283, the coils of the
four quadrants are in four parallels, which gives an internal
resistance equal to one-sixteenth that of the total resistance
of the entire ring.
When the coils are connected in two circuits or series
parallel, it requires only two brushes at two neutral points on
the commutator, for any number of poles; this arrangement is
shown in fig. 269.
=Ques. In general what may be said about the current paths through an
armature?=
Ans. The paths may be in parallel or series parallel according as the
winding is of the lap or wave type.
[Illustration: FIG. 284.--Morday's method of measuring the
variation of voltage around the commutator by use of a single exploring
brush and volt meter. It consists in connecting one terminal of the
volt meter (preferably an electrostatic one) to one brush of the
machine, and the other terminal to the exploring brush, which can be
moved from point to point, readings being taken at each point.]
=Variation of Voltage Around the Commutator.=--There are numerous
ways of determining the value of the induced voltage in an armature
at various points around the commutator. In the method suggested by
Morday, it can be measured by the use of a single exploring brush and a
volt meter as shown in fig. 284.
In this method, one terminal of the volt meter is connected
to one of the brushes of the dynamo, and the other terminal
is joined by a wire to a small pilot brush which can be
pressed against the commutator at any desired part of its
circumference. With the machine running at its rated speed, the
exploring brush is placed in successive positions between the
two brushes of the machine. In each position a reading of the
volt meter is taken and the angular position of the exploring
brush noted.
[Illustration: FIG. 285.--Cross magnetization. This is defined
as lines of magnetic force set up in the windings of a dynamo armature
which oppose at right angles the lines of force created between the
poles of the field magnet. The figure shows this cross flux which is
due to the armature current alone.]
=Ques. How does the voltage vary between successive pairs of
commutator segments?=
Ans. The variation is not constant.
=Cross Magnetization; Field Distortion.=--In the operation of
a dynamo with load, the induced current flowing in the armature
winding, converts the armature into an electromagnet setting up a field
across or at right angles to the field of the machine. This cross
magnetization of the armature tends to distort the field produced by
the field magnets, the effect being known as _armature reaction_. To
understand the nature of this reaction it is best to first consider the
effect of the field current and the armature current separately.
Fig. 285 represents the magnetic flux through an armature at rest,
where the field magnets are separately excited. If the armature be
rotated clockwise, induced currents will flow upward through the two
halves of the winding between the brushes, making the lower brush
negative and the upper brush positive.
=Ques. If, in fig. 285, the current in the field magnet be shut off,
and a current be passed through the armature entering at the lower
brush, what is the effect?=
Ans. The current will divide at the lower brush, flowing up each side
to the top brush. These currents tend to produce north and south poles
on each half of the core at the points where the current enters and
leaves the armature. Hence, there will be two north poles at the top of
the ring and two south poles at the bottom.
=Ques. What effect is produced by the like poles at the top and
bottom of the ring?=
Ans. The external effect will be the same as though there were a single
north and south pole situated respectively at the top and bottom of the
ring.
=Ques. In the operation of a dynamo, how do the poles induced in the
armature affect the magnetic field of the machine?=
Ans. They distort the lines of force into an oblique direction as shown
exaggerated in the diagram fig. 286.
[Illustration: FIG. 286.--Distortion of magnetic field due
to cross magnetization. For clearness, the effect is shown somewhat
exaggerated. A drag or resistance to the movement of the armature is
caused by the attraction of the north and south poles on the armature
and pole pieces respectively.]
=Ques. What effect has the presence of poles in the armature on the
operation of the machine?=
Ans. In fig. 286, the resultant north pole _n_, _n_, _n_, where the
lines emerge from the ring, attracts the south pole, _s_, _s_, _s_,
where the lines enter the field magnet, hence a load is brought upon
the engine, which drives the dynamo, in dragging the armature around
against these attractions. The stronger the current induced in the
armature, the greater will be the power necessary to turn it.
=Ques. Why does this reaction in the armature require more power to
drive the machine?=
Ans. The effect produced by the armature reaction is in accordance
with Lenz's law which states that: _In electromagnetic induction,
the direction of the induced current is such as to oppose the motion
producing it._
[Illustration: FIG. 287.--Actual distortion of field resulting
from cross magnetization, as shown by iron filings.]
=Remedies for Field Distortion.=--Since the distortion of the
magnetic field of a dynamo causes unsatisfactory operation, numerous
attempts have been made to overcome this defect, as for instance, by:
1. Experimenting with different forms of pole piece;
The reluctance of the pole piece should be increased in the
region where the magnetic flux tends to become most dense.
The trailing horn of the pole piece may be made longer than
the advancing horn and cut farther from the surface of the
armature, so as to equalize the distribution of the magnetic
flux.
2. Lengthening the air gap;
This increases the reluctance, and also necessitates more
ampere turns in the field winding. The field distortion,
however, will not be so great, as it would be if the magnetic
field of the machine were weaker.
3. Slotting the pole pieces;
Both longitudinal gaps and oblique slots have been tried. The
reduction of cross section of the pole piece causes it to
become highly saturated and to offer large reluctance to the
cross field.
4. The use of auxiliary poles.
These are small poles placed between the main poles and so
wound and connected that their action opposes that of the cross
field.
=Normal Neutral Plane.=--This may be defined as _a plane passing
through the axis of the armature perpendicular to the magnetic field of
the machine when there is no flow of current in the armature_, as shown
in fig. 288. It is the plane in which the brushes would be placed to
prevent sparking when the machine is in operation were the field not
distorted by armature reaction, and there were no self-induction in the
coils.
=Commutating Plane; Lead of the Brushes.=--It has been found that
in order to reduce sparking to a minimum, the brushes must be placed in
certain positions found by trial and designated as being located in the
_neutral plane_.
When the brushes are in the neutral plane, they are in contact with
commutator segments connecting with coils that are cutting the lines of
force at the minimum rate.
=Ques. Define the term "commutating plane."=
Ans. This is a plane passing through the axis of the armature and
through the center of contact of the brushes as shown in figs. 289 and
300.
=Ques. What is the angle of lead?=
Ans. The angle between the normal neutral plane and the commutating
plane.
In the operation of a dynamo since the field, on account of
armature reaction, is twisted around in the direction of
rotation, the proper position for the brushes is no longer in
the normal neutral plane, but lies obliquely across, a few
degrees in advance. Hence, for sparkless commutation, the
commutating plane is a little in advance of the normal neutral
plane, the lead being measured by the angle between these
planes, as stated in the definition.
[Illustration: FIG. 288.--Normal neutral plane. This is
a reference plane from which the lead is measured. As shown, the
normal neutral plane lies at right angles to the lines of force of an
undistorted field.]
=Ques. What may be said with respect to the angle of lead?=
Ans. _For sparkless commutation, the angle of lead varies with the
load._
If the field be much altered at full load, it is evident that
at half or quarter load it will not be nearly so much twisted,
hence the necessity for mounting the brushes on some kind of
rocking device which will allow them to be shifted in different
positions for different loads. A desirable point, then, in
dynamo design is to make the angle of lead at full load so
small that it will not be necessary to shift the brushes much
for variation of load. This can be accomplished by making the
field magnet field considerably more powerful than the armature
field.
[Illustration: FIG. 289.--Diagram illustrating the
demagnetizing effect of armature reaction. This results from
the forward lead given the brushes in order to secure sparkless
commutation.]
=Demagnetizing Effect of Armature Reaction.=--In the operation
of a dynamo, as previously explained, the position of the brushes for
sparkless commutation must be varied with the load; that is, for light
load they should occupy a position practically midway between the poles
and for a heavy load they must be moved a few degrees in the direction
of rotation. In other words, the commutating plane must be more or less
in advance of the normal neutral plane as shown in fig. 289.
=Ques. What is the effect of lead?=
Ans. It produces a demagnetizing effect which tends to weaken the field
magnets.
=Ques. Describe this demagnetizing effect in detail.=
Ans. Tracing the armature currents, in fig. 289 according to Fleming's
rule, it will be seen that current in inductors 1 to 18 flow _from_
the observer indicated by crosses representing the tails of retreating
arrows and in inductors 19 to 36, _toward_ the observer from the back
of armature, indicated by dots representing the points of approaching
arrows. In determining these current directions the inductors to the
right of the neutral line are considered as moving downward, and those
to the left as moving upward. The current in inductors 1 to 15 and 19
to 33, tends to cross magnetize the magnetic field of the machine, but
the current in inductors 34 to 36 and 16 to 18 tends to produce north
and south poles as indicated. These poles are in opposition to the
field poles and tend to demagnetize them. Hence, the inductors lying
outside the two upright lines are known as _cross magnetizing turns_,
and those lying inside, as _demagnetizing turns_.
The breadth of the belt of demagnetizing turns included between
the two upright lines is clearly proportional to the angle of
lead; therefore, the demagnetizing effect increases with the
lead.
=Eddy Currents; Lamination.=--Induced electric currents, known
as eddy currents, occur when a solid metallic mass is rotated in a
magnetic field. They consume considerable energy and often occasion
harmful rise in temperature. Armature cores, pole pieces, and field
magnet cores are specially subject to these currents.
[Illustration: FIG. 290.--Arago's experiment illustrating
eddy currents. Arago found that if a copper disc be rotated in its
own plane underneath a compass needle, the needle was dragged around
as by some invisible friction. The explanation of this phenomenon,
known as _Arago's rotations,_ is due to Faraday, who discovered that
it was caused by induction. That is, a magnet moved near a solid mass
of metal, induces in it currents, which, in flowing from one point to
another, have their energy converted into heat, and which, while they
last, produce (in accordance with Lenz's law) electromotive forces
tending to stop the motion. Thus, in the figure, there are a pair of
eddies in the part passing between the poles, and these currents oppose
the motion of the disc. Foucault showed by experiment the heating
effect of eddy currents, but such currents were known years before
Foucault's experiments, hence they are incorrectly called Foucault
currents.]
=Ques. Describe the formation of eddy currents.=
Ans. In fig. 291, a bar inductor is seen just passing from under the
tip of the pole piece N of the field magnet. Noting the distribution of
the lines of force, it will be seen that the edge _c d_ is in a weaker
field than the edge _a b_, hence, since the two edges move with the
same velocity, the electromotive force induced along _c d_ will be less
than that induced along _a b_. This gives rise to whirls or current
eddies in the copper bar as shown.
[Illustration: FIG. 291.--Formation of eddy currents in a
solid bar inductor. On account of its appreciable size, the field
is sometimes weaker at one point than another, hence the unequal
electromotive forces thus produced will induce eddy currents.]
=Ques. What should be noted in seeking a remedy for eddy currents?=
Ans. It should be noted that eddy currents are due to very small
differences of pressure and that the currents are large only because of
the very low resistance of their circuits.
=Ques. What is the best means of reducing eddy currents?=
Ans. Lamination.
=Ques. Explain this mode of construction with respect to the bar
inductor fig. 291.=
Ans. In the case of a large bar inductor such as shown in fig. 291, it
could be replaced by a number of small wires soldered together only at
the ends. The layer of dirt or oxide on the outside of the wires will
furnish sufficient resistance to practically prevent the eddy currents
passing from wire to wire.
[Illustration: FIG. 292.--Eddy currents induced in a solid
armature core. Eddy currents always occur when a solid metallic mass
is rotated in a magnetic field, because the outer portion of the metal
cuts more lines of force than the inner portion, hence the induced
electromotive force not being uniform, tends to set up currents between
the points of greatest and least potential. Eddy currents consume
a considerable amount of energy and often occasion harmful rise in
temperature.]
=Ques. How should an armature core be laminated to avoid eddy
currents?=
Ans. It should be laminated at right angles to its axis.
Fig. 292 shows the induced eddy currents in a solid armature
core, and fig. 293 shows the manner in which the paths of these
currents are interrupted and the losses due to their effect
diminished by the use of laminated cores.
[Illustration: FIG. 293.--Armature core with a few laminations
showing effect on eddy currents. In practice the core is made up
of a great number of thin sheet metal discs, about 18 gauge, which
introduces so much resistance between the discs that the formation of
eddy currents is almost entirely prevented.]
In fig. 293, only five laminations or plates are indicated,
so as to show the sub-division of the eddy currents, but in
practical armatures, the number of laminations or punchings
ranges from 40 to 66 to an inch, and brings the eddy current
loss down to about one per cent. A greater increase in the
number of laminations per inch is not economical, however,
owing to the difficulties encountered in the punching and
handling of extremely thin sheets of iron, and the loss of
space between the plates.
Armature cores constructed of the number of plates stated,
and forced together by means of screws and heavy hydraulic
pressure, contain from 80 to 90 per cent. of iron, and have a
magnetic flux carrying capacity only from 5 to 15 per cent.
less than when they are made of an equal volume of solid iron.
=Magnetic Drag on the Armature.=--Whenever a current is induced
in an armature coil by moving it in the magnetic field so as to cut
lines of force, the direction of the induced current is such as to
oppose the motion producing it. Hence, in the operation of a dynamo,
considerable driving power is required to overcome this magnetic drag
on the armature.
[Illustration: FIG. 294.--Circular concentric magnetic field
surrounding a conductor carrying a current. If this conductor be moved
across a magnetic field, as between the poles of a magnet, the lines of
force will be distorted as in fig. 295, which will oppose the motion of
the conductor.]
A conductor carrying a current is surrounded by a circular concentric
magnetic field. If now such a conductor, with current flowing toward
the observer as in fig. 294, be placed in a uniform magnetic field, a
distortion of the magnetic lines will occur as shown in fig. 295. The
resulting mechanical actions are easily determined by remembering
that _the magnetic lines act like elastic cords tending to shorten
themselves_. There is in fact a tension along the magnetic lines and a
pressure at right angles to both, proportional at every point to the
square of their density.
[Illustration: FIG. 295.--Illustrating drag on armature
inductors. In moving a wire carrying a current through a magnetic
field, the lines of force are distorted, and the effect on the wire
is the same as though the magnetic lines were elastic cords tending
to shorten themselves. They, therefore, oppose the motion of the
wire; hence, in dynamo operation, more or less power is absorbed in
overcoming this drag on the numerous inductors. In the figure the
inductor is being moved upward against the "drag" due to the magnetic
field.]
It is evident by inspection of the lines in fig. 295, that there is a
drag upon the conductor in the direction shown by the arrow.
=Smooth and Slotted Armatures.=--The inductors of an armature may
be placed on a smooth drum or in slots cut in the surface parallel to
the axis.
In the first instance, the magnetic drag comes on the inductors and in
the case of slots, upon the teeth.
The effect of embedding the armature inductors in slots is
to distort the magnetic field as shown in fig. 296. Most of
the lines of force pass through the teeth, thus, not only are
the inductors better placed for driving purposes, but, being
screened magnetically by the teeth, the forces acting on them
are reduced, the greater part of the magnetic drag being taken
up by the core.
It should be noted that, although screened from the field, the
inductors in a slotted armature cut magnetic lines precisely
as if they were not protected. The effect is as though the
magnetic lines flashed across the slots from tooth to tooth,
instead of passing across the intermediate slot at the ordinary
angular velocity.
=Comparison of Smooth and Slotted Armatures.=--The slotted
armature has the following advantages over the smooth type:
1. Reduced reluctance of the air gap;
2. Better protection for the winding;
3. Inductors held firmly in place preventing slippage;
4. No magnetic drag on inductors;
5. No eddy currents in inductors;
6. Better ventilation;
7. Opposition to armature reaction.
Due to increased density of flux through the teeth.
The disadvantages of slotted armatures may be stated as follows:
1. Tendency of the teeth to induce eddy currents in the pole pieces;
2. Increased self-induction of the armature coils;
3. Greater hysteresis loss on account of denser flux in the teeth;
4. Leakage of lines of force through the core, especially in the case
of partially enclosed slots.
[Illustration: FIG. 296.--Effect of slotted armature. The
teeth, as they sweep past the pole face, cause oscillations of the
magnetic flux in the iron near the surface because the lines in the
pole piece PP tend to crowd toward the nearest teeth, and will be
less dense opposite the slots. This fluctuation of the magnetic lines
produce eddy currents in the pole faces unless laminated. The armature
inductors, being screened from the field, are relieved of the drag
which is taken by the teeth.]
=Magnetic Hysteresis in Armature Cores.=--When the direction
or density of magnetic flux in a mass of iron is rapidly changed a
considerable expenditure of energy is required which does not appear as
useful work. For instance, when an armature rotates in a bipolar field,
the armature core is subjected to two opposite magnetic inductions in
each revolution; that is, at any one instant a north pole is induced
in the core opposite the south pole of the magnet and a south pole in
the core opposite the north pole of the magnet as indicated in fig.
297 by _n_ and _s_. Accordingly, if the armature rotate at a speed of
1,000 revolutions per minute, the polarity of the armature will be
changed 2,000 times per minute, and result in the generation of heat at
the expense of a portion of the energy required to drive the armature.
This loss of energy is due to the work required to change the position
of the molecules of the iron, and takes place both in the process of
magnetizing and demagnetizing; the magnetism in each case lagging
behind the force.
=Core Loss or Iron Loss.=--These terms are often employed to
designate the total internal loss of a dynamo due to the combined
effect of eddy currents and hysteresis, but as the losses due to the
former are governed by laws totally different from those applicable to
the latter, special analysis is required to separate them.
The eddy current loss per pound of iron in the armature core diminishes
with the thinness of the laminated sheets, and may be made indefinitely
small by the use of indefinitely thin iron plates, were it not for
certain mechanical and economical reasons.
The loss due to hysteresis per pound of iron in the core, does not vary
with the thinness of the core plates; it can be reduced only by the use
of a material having a low hysteretic coefficient.
=Dead Turns.=--The voltage generated in a dynamo with a given
degree of field excitation is not strictly proportional to the speed,
but somewhat below on account of the various reactions. That is, the
machine acts as though some of its revolutions were not effective in
inducting electromotive force.
The name _dead turns_ is given to the number of revolutions by which
the actual speed exceeds the theoretical speed for any output.
Again, this term is sometimes used to denote that portion of the wire
on an armature which comes outside the magnetic field and is therefore
rendered ineffective in inducing electromotive force. The number of
dead turns is about 20% of the total number of turns.
[Illustration: FIG. 297.--Magnetic hysteresis in armature
core. Unlike poles are induced in the core opposite the poles of the
field magnet. Since on account of the rotation of the core the induced
poles are reversed a thousand or more times a minute, considerable
energy is required to change the positions of the molecules of the iron
for each reversal, resulting in the generation of heat at the expense
of a portion of the energy required to drive the armature.]
=Self-induction in the Coils; Spurious
Resistance.=--Self-induction opposes a rapid rise or fall of an
electric current in just the same way that the inertia of matter
prevents any instantaneous change in its motion. This effect is
produced by the action of the current upon itself during variations in
its strength.
In the case of a simple straight wire, the phenomenon is almost
imperceptible, but if the wire be in the form of a coil, the adjacent
turns act inductively upon each other upon the principle of the mutual
induction arising between two separate adjacent circuits.
=Ques. What effect has self-induction on the operation of a
dynamo?=
Ans. It prevents the instantaneous reversal of the current in the
armature coils. That is, the current tends to go on and in fact does
actually continue for a brief time after the brush has been reached.
[Illustration: FIG. 298.--Distribution of magnetic lines
through a ring armature. Since the lines follow the metal of the ring
instead of penetrating the interior, no electromotive force is induced
in that portion of the winding lying on the interior surface of the
ring. There is, therefore, a large amount of dead wire or wire that
is ineffective in inducing electromotive force; this is the chief
objection to the ring type of armature.]
=Ques. What becomes of the energy of the current at reversal?=
Ans. The energy of the current in the section of the winding undergoing
commutation is wasted in heating the wire during the interval when it
is short circuited, and as it passes on, energy must again be spent in
starting a current in it in the reverse direction. There is, then, a
lagging of the current in the armature coils due to self-induction.
=Ques. What is spurious resistance?=
Ans. This is an apparent increase of resistance in the armature
winding, which is proportional to the speed of the armature, and due to
the lagging of the current.
[Illustration: FIG. 299.--Distribution of magnetic lines
through solid drum armature of a four pole machine.]
=Armature Losses.=--The mechanical power delivered to the pulley
of a dynamo is always in excess of its electrical output on account of
numerous mechanical and electrical losses. Mechanical losses result
from:
1. Friction of bearings;
2. Friction of commutator brushes;
3. Air friction.
The electrical losses may be classified as those due to:
1. Armature resistance;
2. Hysteresis;
3. Eddy currents.
=Ques. How do the mechanical and electrical losses compare?=
Ans. The mechanical losses are small in comparison with the electrical
losses.
=Ques. What may be said with respect to friction?=
Ans. The bearing friction varies with the load. In calculating this
loss not only must the weight of the armature be considered but also
the belt tension and magnetic attraction in order to get the resultant
thrust on the bearing. Friction of the brushes is very small and may be
neglected. A small loss of power is caused by the friction of the air
on the armature. The latter, since it revolves rapidly, acts to some
extent as a fan, and in some machines this fan action is made use of
for ventilation and cooling.
=Ques. How are the other losses determined?=
Ans. The loss of power due to armature resistance is easily found
by Ohm's law, but the hysteresis and eddy current losses, known
collectively as _iron losses_, are not so easily determined. If the
magnetization curve of the particular quality of iron used for armature
plates be known, the hysteresis loss may be calculated approximately.
Eddy current losses are the most important, especially in large
machines. As previously explained, in all the moving metal masses
unless laminated, there will be eddy currents set up if they cut
magnetic lines. Power may be lost from this cause even in the metal of
the shaft if there be leakage of magnetic lines into it.
CHAPTER XX
COMMUTATION AND THE COMMUTATOR
The act of commutation needs special study. If it be incorrectly
performed, the imperfection at once manifests itself by sparks which
appear at the brushes. In the study of this chapter on commutation it
would be advisable for the student to first review the basic principles
of commutation as given in chapter XIV, which contains a brief and
simple explanation of how the alternating current in the armature is
converted into direct current by the action of the commutator.
=Ques. What is the period of commutation?=
Ans. The time required for commutation, or the angle through which the
armature must turn to commute the current in one coil.
=Ques. Upon what does the period of commutation depend?=
Ans. Upon the width of the brushes as shown in fig. 300.
This fixes the angle through which the armature must revolve
to commute the current in one coil. This angle is formed, as
shown in the figure, by two intersecting planes, M and S, which
pass through the axis of the armature and the two edges of the
brush. Commutation then, begins at M and ends at S.
=Ques. What is the position of the commutating plane with respect to
M and S, in fig. 300?=
Ans. It bisects the angle formed by the planes M and S.
[Illustration: FIG. 300.--Armature with one brush in position
to illustrate the _period of commutation_ and _commutating plane_. The
latter is called "commutating line" by some writers. The period of
commutation depends on the thickness of the brush end in contact with
the commutator. Careful distinction should be made between _commutating
plane_, _neutral plane_, and _normal neutral plane_ as defined
elsewhere.]
=Ques. What is the the commutating plane?=
Ans. An imaginary plane passing through the axis of the armature and
the center of contact of the brush.
=Ques. What two planes are referred to in stating the position of the
brushes?=
Ans. The normal neutral plane and the commutating plane.
The angle intercepted by these two planes represents the
_lead_, thus in stating that the brushes have a lead of 6°,
means that the angle intercepted by the normal neutral plane
and the commutating plane is 6°.
[Illustration: FIG. 301.--The proper position of the brushes,
if there were no field distortion and self-induction in the armature
coils, would be in the normal neutral plane. In the actual dynamo
these two disturbing effects are present which makes it necessary to
advance the brushes as shown in figs. 302 and 303 to secure sparkless
commutation.]
=Ques. What is the difference between the normal neutral plane and
the neutral plane?=
Ans. This is illustrated in figs. 301 and 302. _The normal neutral
plane is the position of zero induction assuming no distortion of
the field_ as in fig. 301. _The neutral plane is the position of zero
induction with distorted field_ as in fig. 302 and as is found in
the actual machine; the distortion is exaggerated in the figure for
clearness.
[Illustration: FIG. 302.--Brush adjustment for field
distortion. The effect of the latter is to twist the lines of force
around in the direction of rotation, thus maximum induction takes place
in an inclined plane. The brushes then must be advanced to the _neutral
plane_ which is at right angles to the plane of maximum induction. This
gives the proper position of the brushes _neglecting self-induction_.]
=Ques. What is the normal plane of maximum induction?=
Ans. _A plane, 90° in advance of the normal neutral plane_, being the
position of maximum induction with no distortion of field, as in fig.
301.
=Ques. What is the plane of maximum induction?=
Ans. _A plane 90° in advance of the neutral plane_, being the position
of maximum induction in a distorted field as in fig. 302.
[Illustration: FIG. 303.--Brush adjustment for self-induction.
For convenience an electric current is regarded as having weight and
hence possessing the property of inertia. The current then during
commutation cannot be instantly brought to rest and started in the
reverse direction but these changes must be brought about gradually
by an opposing force. Hence by advancing the brushes beyond the
neutral plane as illustrated, commutation takes place with the short
circuited coil cutting the lines of force so as to induce a current in
the opposite direction; this opposes the motion of the current in the
short circuited coil, brings it to rest and starts it in the opposite
direction, thus preventing sparks. Figs. 301 to 303 should be carefully
compared and thoroughly understood.]
=Ques. What should be noted with respect to the different planes?=
Ans. The commutating plane should be carefully distinguished from the
normal neutral plane and from the neutral plane, as shown in fig. 303.
=Commutation.=--In order to understand just what happens during
commutation, a section of a ring armature may be used for illustration,
such as shown in fig. 304. Here the coils A, B, C, D, E, are connected
to commutator segments 1, 2, 3, 4, and the positive brush is shown
in contact with two segments 2 and 3, the brush being in the neutral
position. Currents in the coils on each side of the neutral line flow
to the brush through segments 2 and 3; the brush then is positive.
[Illustration: FIG. 304.--Commutation. This takes place during
the brief interval in which any two segments of the commutator are
bridged by the brush. The coil connecting with the two segments under
the brush is thus short circuited. During commutation the current in
the short circuited coil is brought to rest and started again in the
reverse direction against the opposition offered by its so called
inertia, or effect produced by self-induction.]
Now, as the armature turns, the commutator segments come successively
into contact with the brush. In the figure, segment 3 is just leaving
the brush and 2 is beginning to pass under it, hence, for an instant
the coil C is short circuited.
=Ques. In fig. 304, what are the current conditions?=
Ans. Previous to contact with segment 2, current flowed in coil C in
the same direction as in coil B.
=Ques. What occurs while the brush is in contact with segments 2 and
3?=
Ans. During this brief interval, the current in C is stopped and
started again in the opposite direction.
Similarly each coil of the armature as it passes the brush will
be short circuited and have its current reversed. This is known
as _commutation_.
=Ques. What is the effect of field distortion with respect to
commutation?=
Ans. The neutral plane no longer coincides with the normal neutral
plane but is advanced in the direction of rotation of the armature as
shown in fig. 302.
The reaction of the poles N' and S' of the armature field on
the poles S and N of the main magnetic field tends to crowd
the lines of force into the upper pole face of the south pole
of the magnet, and into the lower pole face of the north pole.
This effect is due to the strong magnetic attraction between
the opposite poles S and N' and N and S', and the equally
strong repulsion between like poles N and N' and S and S'.
Hence, the plane of maximum induction no longer coincides
with the normal plane of maximum induction, but is advanced
in the direction of rotation, depending upon the strength of
the armature current, being shifted forward for an increase
of current, and backward for a decrease of current. This
distortion of the field and the consequent shifting of the
plane of maximum induction naturally results in the shifting of
the neutral plane from the vertical position to the inclined
position as shown.
=Position of the Brushes; Sparking.=--In accordance with the
laws of electromagnetic induction, if the bipolar ring armature shown
in fig. 301 be rotated in the direction indicated by the arrow the
armature current entering at the brush E will divide, one part passing
through the coils on the right half of the ring, and the other part
through the coils on the left half of the ring, to the brush F, from
which the total current will pass out, urged by the full value of the
electromotive force induced in all the coils on both halves of the ring.
[Illustration: FIGS. 305 to 308--Improper brush adjustment
resulting in excessive sparking. When the brushes are not advanced far
enough, commutation takes place before the short circuited coil reaches
the neutral plane, hence, its motion is not changed with respect
to the magnetic field so as to induce a reverse current till after
commutation. There is then no opposing force, during commutation, to
stop and reverse the current in the short circuited coil, and when the
brush breaks contact with segment 1, as in fig. 308, the "_momentum_"
of the current in coil F causes it to jump the air gap from segment 1
to segment 2 and the brush, against the enormous resistance of the air,
thus producing a spark whose intensity depends on the momentum of the
current in coil F. Sparking, if allowed to continue, will injure the
brushes and commutator segments.]
Again, if the brushes be placed at the points G and H, each half of a
current entering at G, will pass through one-half of the coils on the
left side and one-half of the coils on the right side of the ring, so
that each half of the current will be urged forward by an electromotive
force equal to the electromotive force tending to force it back, and
therefore, no current will pass in or out through the brushes. From
these considerations it is obvious that the proper position for the
brushes would be in the normal neutral plane, _were it not for the
disturbing effects of armature reaction and self induction of the
current_.
=Ques. Should the brushes of a dynamo be placed in the neutral
plane?=
Ans. No.
=Ques. Why not?=
Ans. The brushes must be advanced beyond the neutral plane to prevent
sparking.
=Ques. What is the cause of sparking at the brushes?=
Ans. It is due to _self-induction_ in the coil undergoing commutation.
=Ques. Explain the effect of self-induction in detail.=
Ans. When commutation takes place with the brushes in the neutral
plane as in fig. 304, there will be no voltage induced in the short
circuited coil C. The current, therefore, which flowed in coil C before
it was short circuited will cease, and as segment 3 breaks contact with
the brush, it will be thrown as a perfectly idle coil upon the right
hand half of the ring in which a current is flowing toward the brush.
Moreover, the current which was flowing through D and 3 directly to the
brush, must suddenly traverse the longer path through the idle coil C.
Now, on account of self-induction, _the current acts in precisely the
same manner as though it had weight_; that is:
_It cannot be instantly stopped or started._
[Illustration: FIGS. 309 to 313.--How sparkless commutation is
obtained by advancing the brushes beyond the neutral plane; commutation
progressively shown.]
[Illustration: FIG. 309.--Commutation begins; current flows
up both sides of the armature, uniting at S and flowing to the brush
through commutator segment 1 as indicated by the arrow.]
[Illustration: FIG. 310.--Segment 2 has come into contact
with the brush and coil F, in which commutation is taking place, is
now short circuited. The current now divides at M, part passing to
the brush through segment 2, and part through coil F and segment 1.
Although coil F is short circuited and having passed the neutral plane,
is cutting the lines of force so as to induce a current in the opposite
direction, it still continues to flow with unchanged direction against
these opposing conditions. This is due to _self-induction_ in the coil
which resists any change just as the momentum of a heavy moving body,
such as a train of cars, offers resistance to the action of the brakes
in retarding and stopping its motion.]
Therefore, when segment 3 leaves the brush, the current will not
instantly change its path and flow through C, but will be urged by its
"_momentum_," and jump the air gap between the brush and segment 3,
thus producing a spark.
[Illustration: FIG. 311.--Segment 2 has moved further under
the brush, and the opposition offered to the forward flow of the
current in the short circuited coil F by the reverse induction in the
magnetic field to the right of the neutral plane has finally brought
the current in F to rest. The currents from each side of the armature
now flow direct to the brush through their respective end segments 1
and 2.]
[Illustration: FIG. 312.--Segment 1 is now almost out of
contact with the brush. A current has now been started in the coil F
in the reverse direction due to induction in the magnetic field to the
right of the neutral plane; it flows to the brush through segment 2.
The current has not yet reached its full strength in F, accordingly,
part of the current coming up from the right divides at S and flows to
the brush through segment 1.]
[Illustration: FIG. 313.--Completion of commutation in
segments 1 and 2; the brush is now in full contact with segment 2, the
current in coil F has now reached its full value, hence the current
flowing up from the right no longer divides at S but flows through F
and segment 2 to the brush. If the current in F had not reached its
full value, at the instant segment 1 left contact with the brush, it
could not immediately be made to flow at full speed any more than could
a locomotive have its speed instantly changed. This, as previously
explained, is due to self-induction in the coil or the so called
"inertia" of the current which opposes any sudden change in its rate of
flow or direction. Accordingly that portion of the current which was
flowing up from the right and passing off at S to the brush through
segment 1 as in fig. 312, would, when this path is suddenly cut off as
in fig. 313, encounter enormous opposition in coil F. Hence, it would
momentarily continue to flow through segment 1 and jump the air gap
between this segment and the brush, resulting in a more or less intense
spark depending on the current conditions in coil F.]
=Ques. How may this sparking be prevented?=
Ans. If the brushes be given additional lead, that is shifted further
to the right to some position as N N, fig. 304, coil C will not
remain idle during the interval it is short circuited, _but will
cut the magnetic lines in such a way as to induce a current in the
reverse direction through it_. Under these conditions, when segment 3
breaks contact with the brush, the current flowing through D does not
encounter an idle coil, but one in which a current is flowing in the
same direction, hence, the tendency to jump the air gap and produce a
spark is reduced; with proper adjustment of the brushes, there will be
no sparking.
=Ques. What is the objection to very thin brushes?=
Ans. Time must be allowed for reversal of the current, hence the
brushes must not be so thin as merely to bridge the insulation between
segments.
=Ques. What is the effect of lead?=
Ans. There is usually much sparking when the lead is too small; a
little sparking when too great, and no sparking when just right. If the
lead be excessive, there is a waste of energy due to the generation of
a larger reverse current in the short circuited coil than is necessary.
=Fixed Position of Brushes.=--The condition for sparkless
commutation is that the current in the short circuited coil be reduced
to zero, and increased in the opposite direction up to the same value
as that in the next coil leading. If the brushes are to remain in a
fixed position, this condition will only be realized at the particular
load for which the brushes are set. Thus, if the brushes be set for
the average load, the reversing field will not be correct for either
a weaker or stronger load. Hence, sparkless commutation with fixed
brushes must be due to some other factor.
=Ques. What may be said with respect to carbon brushes?=
Ans. Since carbon possesses a high resistance, the drop will vary
greatly with the contact area, thus affecting a difference of potential
in the two segments passing under the brush and it is largely to this
that sparkless commutation is due.
=Ques. What is the effect of resistance on commutation?=
Ans. In fig. 304 during commutation, that is, while the brush contacts
with any two segments, as 2 and 3, the currents coming up through the
winding on either side of the neutral plane are offered two paths to
the brush: 1, direct to brush through the connecting segment, or 2,
across the short circuited coil and adjacent segment. Thus, on the
right side: to brush through segment 3, or across coil C and adjacent
segment 2.
_The current will take the path of least resistance._
At the beginning of commutation, almost the entire brush area being in
contact with segment 3, the contact resistance of this segment will
be much less than for segment 2; hence, not only will the current
at the right flow through 3, but also the current at the left after
first traversing the short circuited coil. As commutation progresses,
the area of contact of 3 decreases while that of 2 increases, and
the respective resistances vary in inverse proportion. Likewise the
tendency of the current in the left half of the winding to take the
longer path through coil C and segment 3 to the brush gradually
decreases, becoming zero when the two contact areas become equal.
During the second half of the period of commutation, the contact area
of segment 2 becomes greater and of 3, less; thus the resistance of 2
is lowered, and that of 3 increased. Accordingly, all of the current
at the left will flow through segment 2, and the current at the right
will flow through C and 2 rather than through 3. In this way the
current is reversed in C, and, if the brush be broad enough to allow
a sufficient time interval, the current in C is built up to its full
value before segment 3 leaves the brush, thus securing sparkless
commutation.
This contact resistance factor in sparkless commutation
is illustrated in figs. 314 to 318, it being assumed that
during commutation, the brush contact resistance is inversely
proportional to the area of contact, and that the winding is
free of resistance and inductance. The current is taken as 40
amperes, in which case 20 amperes will flow from each side of
the winding to the brush.
In fig. 314 the instant before commutation begins all the
current will flow through segment A. At the end of the first
quarter of the period of commutation, fig. 315, 30 amperes will
flow from the right to brush through A, and from the left, 10
amperes through the short circuited coil via A and 10 amperes
through B.
At the end of the second quarter or half period, fig, 316, the
current through each half of the winding will flow to the brush
through these respective segments.
At the end of the third quarter, fig. 317, the current from the
right will divide, 10 amperes going through A, and 30 amperes
traversing the short circuited coil and out through B. The
entire current from the left will flow through segment B.
At the end of the fourth quarter, fig. 318, or completion of
the period the current from each half of the winding will flow
to the brush through B.
[Illustration: FIGS. 314 to 318.--Brush contact resistance
theory of commutation, neglecting self-induction and resistance in the
coils. The total current is assumed to be 40 amperes made up of 20
amperes flowing toward the brush from the coils on the right and 20
amperes from the coils on the left. During commutation, that is, the
interval during which the brush contacts with any two adjacent segments
of the commutator, the current is assumed to vary directly as the
contact area.]
[Illustration: FIG. 314.--Beginning of commutation; segment A
is entirely under the brush, and B is at the initial point of contact.
For this position the currents from both sides flow to the brush
through segment A.]
[Illustration: FIG. 315.--One-quarter period of commutation.
One quarter of the brush area is in contact with B and three quarters
in contact with A; hence, 10 amperes will flow through B and 30 amperes
through A.]
[Illustration: FIG. 316.--Second quarter of commutation
period. The brush now contacts equally with both segments, hence 20
amperes will flow through each segment.]
[Illustration: FIG. 317.--Third quarter of commutation period.
Three quarters of the brush area is in contact with segment B and one
quarter with segment A; accordingly, 30 amperes will flow through B and
10 amperes through A.]
[Illustration: FIG. 318.--Completion of commutation. The brush
is in full contact with segment B and at the point of breaking contact
with A, hence the entire current from both sides or 40 amperes will
flow through B.]
[Illustration: FIGS. 319 to 323.--Brush contact theory of
commutation for case in which the brush covers two segments of the
commutator. Fig. 319 beginning of commutation; fig. 320 one-quarter
period; fig. 321, one-half period; fig. 322, three-quarter period; fig.
323 completion of commutation.]
=Ques. What is the effect of increasing the degree of contact of the
brushes?=
Ans. It lengthens the period of commutation, and permits it to start
in one coil before the preceding coil has entirely passed through this
stage.
The effect of changing the degree of contact is shown in figs.
319 to 323, in which the width of the brush is made equal to
that of two segments.
=Construction of Commutators.=--The commutator for a closed coil
armature consists of a number of segments or L-shaped bars C of drop
forged hard drawn copper assembled around a tubular iron hub as shown
in figs. 324 and 325. The bars are held in position by the nuts E, and
washers F, screwed on the ends of the tube D. The bars are insulated
from each other and from the washers by mica as shown by the heavy
lines G, and they are also insulated from the tube either by a tube
of mica H, or by a sufficient air space. The ends of the sections
of winding are connected to the vertical portions of the bars K, by
insertion in the slots L, where they are securely held in place by
means of the binding screws, which for greater security are soldered
together, and may be released from the slots, whenever necessary, by
the application of a hot soldering iron.
[Illustration: FIGS. 324 and 325.--Side and end sectional
views of commutator showing construction. The parts are: C, segments;
D, tubular iron hub; E, end nuts; F, clamps; G, insulation; L, riser
connection.]
It is very important that all the parts of the commutator should be
fitted together perfectly and screwed up tightly, in order to prevent
looseness. Commutator segments are often made with the washers E,
projecting beyond the ends, but such construction reduces the effective
length of the commutator, therefore the under cut form of bar is
preferable.
In the construction of commutators, the conditions of operation require
that there be:
1. Adequate insulation;
It is necessary to have good insulation between each segment,
and a specially good insulation between the segments and the
hub or sleeve on which they are mounted; also between the
segments and end clamps. The insulating material must not
absorb moisture, hence asbestos, plaster, or vulcanized fibre
are not used. The end insulating rings are usually built up
of mica and shellac, moulded while hot under pressure to the
correct shape.
[Illustration: FIG. 326.--Front view of Western Electric
Commutator for bar wound armature. This commutator is made of hard
drawn copper and insulated throughout, ventilating spaces being
provided near the shaft.]
2. Rigidity against centrifugal force;
Since the segments are subject to centrifugal force, they
must be securely clamped in place. Screws cannot be used, for
that would destroy the insulation. They are therefore held in
place by insulated clamps as shown in fig. 324. These clamps
should be strong and capable of holding the segments firmly in
position, for if a segment should rise out of its place through
centrifugal force, it would disturb the action of the brush and
cause sparking.
3. Provision for wear.
The segments should be of considerable radial depth, so that
the commutator may be turned down from time to time to preserve
its circular form.
[Illustration: FIG. 327.--Sectional view of a General
Electric commutator. The segments are of rolled or forged copper and
are separated by soft mica insulating sheets. This mica must wear
down evenly with the copper, hence its consistency is important. The
segments are wedge shaped so that when drawn radially inward they
support each other like the stones of an arch. They are drawn together
by hollow cone collars which bear upon lugs projecting from the ends
of the segments. These lugs are turned to form a smooth cone after the
segments are assembled. The collars are insulated with mica from the
segments and they are held in place by nuts upon the commutator shell
or by bolts passing from end to end under the segments. The segments
are also provided with lugs for connection to the windings.]
=Points Relating to Commutators.=--1. The number of commutator
segments depends on the scheme of winding and on the number of sections
in the armature winding.
2. Increasing the number of bars diminishes the tendency to spark, and
lessens the fluctuations of the current.
There are two practical reasons for not using a very great
number of segments: it increases the cost, and in small
machines the segments would be so thin that a brush of the
proper thickness to collect the current would lap over, or
bridge several segments.
=Types of Commutator.=--Commutators are made in various forms, but
they may be grouped into two general types:
1. Commutators for closed coil armatures;
These consist of a large number of segments or bars, insulated
from each other and varying in number according to the scheme
of armature winding, and on the number of sections into which
that winding is grouped.
[Illustration: FIG. 328.--A large current low voltage bipolar
dynamo built for electrolytic work and here shown to illustrate the
large size commutator and brushes necessary to collect the large
current. Carbon brushes would not be suitable for this class of machine
because even with copper brushes, whose conductivity is much higher
than carbon, the commutator must be of considerable size to give the
required brush contact area. The contrast between the axial lengths of
the armature and the commutator is very marked. The rocker construction
is of the ordinary type, and heavy flexible cables conduct the current
from the brush holders to the fixed terminals. The machine here
illustrated gives 310 amperes at 7 volts when running at a speed of
1400 R. P. M., corresponding to an output of 2.17 kilowatts.]
2. Commutators for open coil armatures;
This form of commutator is used on some machines designed
especially for arc lighting, such as the Brush and
Thompson-Houston machines. They consist of a comparatively
small number of segments each of which covers a wide angle, and
are separated from each other by air gaps.
3. The segments should be of considerable depth to permit returning
occasionally so that their circular form may be preserved;
4. The insulating material must be such that it will not absorb oil or
moisture;
Mica is best adapted for insulation, but as there are a great
many varieties, differing greatly in hardness and other
equalities, it is important to select the kind that wears at
the same rate as the segments. If the mica be too hard, the
wearing of the segments will leave it projecting and prevent
proper contact with the brushes; again, if the mica be too
soft, it will result in furrows or depressions between the
segments into which copper dust will collect, causing short
circuits.
CHAPTER XXI
=BRUSHES AND THE BRUSH GEAR=
With respect to construction, brushes may be broadly classified as: 1,
those made of metal, and; 2, those made of carbon. There are several
varieties of metal brush, such as:
1. Gauze brushes;
2. Wire brushes;
3. Laminated or strip brushes.
=Gauze Brushes.=--These are very flexible and yielding, their use
being attended with little wear of the commutator.
=Ques. What is the construction of a gauze brush?=
Ans. A gauze brush is made up of a sheet of copper gauze, folded
several times, with the wires running in an oblique direction, so
as to form a solid flat strip of from ¼ to ½ inch in thickness,
increasing with the volume of the current to be collected.
=Ques. What is the object of folding the gauze with the wires running
in oblique directions?=
Ans. It is to prevent the ends of the brush fraying or threading out,
which would be the case if the gauze were folded up in any other
manner.
=Ques. What are the features of gauze brushes?=
Ans. They make good contact, but are quite expensive. They may be set
either tangentially or radially, the latter preferably, since the point
of contact remains the same as the brushes wear away.
[Illustration: FIGS. 329 to 332.--Various forms of brush. Fig.
329 gauze brush; fig. 330 laminated or strip brush; fig. 331 strip and
wire brush as used on the early Edison machines; fig. 332 carbon brush.
Carbon is preferred to copper for brushes on account of the reduction
of sparking secured by its use.]
=Wire Brushes.=--This class of brush, which was extensively used
before the invention of the gauze brush, is made up of a bundle of
brass or copper wires, laid side by side and soldered together at one
end. Since wire brushes are harder than the gauze brush, they are more
liable to cut or score the commutator, and are also more troublesome to
trim.
=Laminated or Strip Brushes.=--These probably represent the
simplest form of brush, but are not extensively used owing to the lack
of flexibility. They consist of a number of strips of copper or brass,
laid one upon the other and soldered at one end, as in fig. 330.
[Illustration: FIG. 333.--General Electric brush holder.
The brush holder yoke consists of a cast iron ring of elliptical
section, supported from the bracket of the end shield in such a manner
as to facilitate the shifting of the brushes. It is provided with a
suitable handle, and may be fastened in any position by means of a
thumb nut on the outside of the bracket. It is so constructed that the
tension on the individual brush can be adjusted without lifting the
brush from the commutator and without the use of tools. The brush can
be removed while the machine is running, without moving the holder
on the stud and without disturbing any other brush. Removal of the
brushes for inspection can be accomplished without permanent change
in the adjustment of the tension of the brush holder spring. The
connection between the brush and stud is made through a flexible copper
connection.]
=Ques. What name is generally given to strip brushes?=
Ans. They are commonly and erroneously called _tangential brushes_,
but they are really beveled at the end and set inclined to the line of
tangency so that the ends of all the sheets will make contact.
In the Brush and Thomson-Houston arc dynamos, in which the
current is limited to ten amperes, the brushes consist of a
simple strip of flexible sheet copper, the ends of which are
slit in a number of places so as to insure contact at several
points.
[Illustration: FIG. 334.--Crocker-Wheeler brush holder. The
carbon brush B is firmly clamped in the "box" C by two screws which
bear on a sheet of brass to protect the carbon from being broken by the
ends of the screws. The box C is carried by four flexible springs S S,
one at each corner and formed of hard copper leaves. These are fixed at
one end to the box and at the other to the solid base which is in one
piece with the spoke attached to the rocker ring. An adjusting screw
passes through appropriate lugs on the box C and loosely through the
head A of a fixed arm _a_. Between the lower surface of _a_ and the
upper lug on the box C is placed the pressure spring.]
=Carbon Brushes.=--When metallic brushes are used upon the
commutators of high tension machines, they frequently give rise to
excessive sparking and also heating of the armature, the metallic dust
given off appearing to lodge between the segments of the commutator,
thus partially short circuiting the armature. To obviate this, carbon
brushes are extensively used in such dynamos, this material being found
very effectual in the prevention of sparking.
=Ques. What is the usual form of carbon brushes?=
Ans. They are usually in the form of oblong blocks.
[Illustration: FIG. 335.--Perspective views of Crocker-Wheeler
brush holder. This holder is of the parallel type in which the brushes
may be adjusted without affecting the lead. Each brush is held rigidly
in its box and there are no sliding contacts in the path of the
current. The holder is further described under fig. 334.]
=Ques. How are they adjusted on the commutator?=
Ans. They are set "butt" end on the commutator, and fed forward as they
wear away by means of a spring holder.
=Ques. Why are carbon brushes so extensively used?=
Ans. Because they are the only form of brush that will give good
commutation with fixed lead.
=Ques. What may be said of the different grades of carbon in use for
brushes?=
Ans. The very soft carbon leaves a layer of graphitic matter on the
commutator, and at high voltages, this may cause sparking; such grade
of carbon should only be used on low voltage machines.
[Illustration: FIG. 336.--Western Electric box type brush
holder. The box which holds the brush is broached to allow the brush
to slide freely, but not loosely, to and from the commutator against
which it is normally held by a lever acting directly upon the brush
head. This avoids the possibility of uneven bearing on the commutator,
as the brushes are allowed very slight lateral or angular motion. The
adjustment of a brush is also simplified after it has been removed
and then replaced. Tension on the brush head is obtained by a special
spring which maintains any given tension for which it may be set. An
auxiliary flat steel spring on the lower side of the lever acts as a
shock absorber between the lever and the brush head, absorbing all
minor vibrations caused by a worn commutator. Side contact between
brush and brush holder is not relied upon to carry the current,
flexible copper pigtails performing this function to the exclusion of
sliding contacts or tension springs, in order to reduce the brush loss.
It is not necessary to take the brush rigging apart or loosen cable
connections when it is desired either to remove or reverse the brushes
to change the direction of armature rotation.]
=Ques. How are the ends of carbon brushes treated and why?=
Ans. They are usually covered at their upper part with a coating of
electro-deposited copper to insure good contact with the holder.
=Comparison of Copper and Carbon Brushes.=--Copper brushes tend to
tear and roughen the surface of the commutator, while carbon brushes
tend to keep the surface smooth. Copper
Cite this
N. Hawkins. "Hawkins Electrical Guide v. 02 (of 10)". Project Gutenberg. Public domain in the USA. https://www.gutenberg.org/ebooks/48846 JSON record · API collection · BibTeX · RIS · CSL-JSON · citation policy